- ECONOMICAL CHLORINATION
- FINEST MATERIALS OF CONSTRUCTION
- ALL VACUUM OPERATION
- WORLDWIDE REPRESENTATIVES AND FACTORY TRAINED SERVICE
- CYLINDER OR MANIFOLD MOUNTING FEATURING ONE SIMPLE CONNECTION
- STANDARD RANGE OF FEED RATES UP TO 500 PPD (10KG/HR)*
APPLICATIONS
MUNICIPAL WATER AND WASTEWATER TREATMENT
For disinfection of potable water in small, municipal, private, or domestic systems ; as well as hotels, resorts, housing projects and farm irrigation systems. An excellent chlorinator for small or private wastewater treatment systems and lift stations in large plants.
INDUSTRIAL WATER AND WASTEWATER TREATMENT
For small industrial water and wastewater treatment including : treatment of metal- finishing wastes, cooling water disinfection, chlorination or boiler make-up water, and process and discharge water of paper, food canning, brewing, bottling, and chemical-process plants.
FEATURES
ECONOMY
At last, a high quality yet economical low capacity chlorinator. Proof that quality does not have to be expensive.
SAFETY
All-vacuum operation. Remote ejector and direct cylinder mounting insures the highest degree of operator safety.
CONSTRUCTION
Fine silver rate valve and inlet valve provide long life and accurate control. All machined body parts produce the most durable chlorinator available.
UNINTERRUPTED TREATMENT
The availability of automatic switchover provides uninterrupted treatment. This feature permits changing used cylinders at the operator’s convenience without stopping the chlorine supply.
SYSTEM INSTALLATION AND FIELD UPGRADING
The self-aligning yoke mounts the regulator directly on a gas cylinder or header valve.
The ejector is designed for installation at the point of application, eliminating the need for lengthy pressurized solution lines.
The gas flowmeter may be remotely located for operator convenience.
The system can easily be field upgraded for automatic flow proportioning, residual or compound loop control
TECHNICAL DATA SHEET
ACCURACY
Within 4% of maximum flowmeter capacity
OPERATING RANGE
20:1, manual
or 10:1, automatic
OPERATING TEMPERATURE
Ejector, 35° F to 120° F;
Other components, -20° F to 120° F
TUBING CONNECTIONS
3/8” vacuum and vent
BACK PRESSURE
Maximum back pressure at point of application for a standard ejector is 140 psig. For greater pressures, consult factory.